Wet Dust Collectors and Scrubbers for Coal Fired Boilers

XBOILER COMPANY industrial boiler
Wet Dust Collectors and Scrubbers for Coal Fired Boilers

Wet dust collectors do two jobs at once on a coal boiler: they remove fine particulate that cyclones miss, and they absorb part of the sulfur dioxide and hydrogen chloride in the flue gas. They also produce wastewater, consume water and corrode anything made of ordinary carbon steel. Used in the right place they are efficient and cheap to run; used as a substitute for a bag filter they create a river of problems.

The main types and what they achieve

The water film scrubber is the simplest: flue gas passes through a chamber whose walls are wetted by an overflow weir, and particles impinge on the film. Efficiency is 85-92% for particles above 5 micrometres, pressure drop 300-600 Pa, and water consumption 0.05-0.1 L per Nm3 of gas.

The venturi scrubber accelerates gas to 60-90 m/s in a throat where water is injected; the shear breaks the water into fine droplets that capture submicron particles. Efficiency reaches 95-99%, but at a pressure drop of 3-6 kPa, which costs 8-20 kW on a 10 t/h boiler.

Every wet collector needs a droplet separator downstream, usually a chevron or cyclone type, or the stack carries entrained water and the plume reads as particulate on the opacity monitor. Carry-over also wets the ID fan, which is where most corrosion failures begin.

Cyclone water-film and spray-tower designs sit between the two, and the tray or packed tower used for desulfurization achieves 90-95% SO2 removal with a calcium or magnesium slurry at a liquid-to-gas ratio of 2-5 L/Nm3.

Performance comparison

Type Particulate removal Pressure drop Water use (L/Nm3) SO2 removal
Water film 85-92% 300-600 Pa 0.05-0.10 10-20%
Cyclone water film 90-95% 800-1,200 Pa 0.10-0.20 15-30%
Venturi 95-99% 3,000-6,000 Pa 0.15-0.30 20-40%
Spray tower with alkali 90-95% 600-1,000 Pa 1.0-2.0 80-95%
Tray scrubber 95-98% 1,200-1,800 Pa 1.5-3.0 90-95%

The numbers assume a cyclone or multi-tube pre-collector ahead of the scrubber. A wet collector fed with 3 g/Nm3 will meet its efficiency figure and still emit 60-150 mg/Nm3, which misses a 30 mg/Nm3 limit.

Water, wastewater and the hidden operating cost

Water consumption is the first thing to calculate. A 10 t/h boiler moving 30,000 Nm3/h of flue gas through a venturi at 0.2 L/Nm3 uses 6 m3/h of water, of which perhaps 0.5-1.5 m3/h must be bled to control dissolved solids and chloride. That bleed is acidic, loaded with fly ash, and cannot go to a municipal drain without neutralisation and settling.

A three-stage settling pond with pH adjustment to 6-9 and a sludge dewatering step is the minimum. Plants that skip it end up cleaning the recirculation nozzle every week, because suspended solids abrade the pump and block the spray pattern.

Water quality matters as much as quantity. Make-up above 500 mg/L chloride attacks 316L and scales the nozzles; a softener ahead of the pond and a 10% continuous bleed hold the loop stable at a fraction of the cost of a rebuild.

Corrosion and cold-end protection

Wet flue gas below the acid dew point attacks carbon steel within months. Wetted sections should be FRP, rubber-lined steel or 316L, and the outlet duct should be sloped with a drain so condensate does not pool. Recirculating scrubber water raises its chloride concentration, which accelerates pitting on stainless steel; bleed rate and chloride monitoring matter more than the alloy choice.

In Henan, winter ambient down to -8°C freezes exposed water lines and the pond surface. Trace heating on the recirculation line and a covered pond are cheaper than a February shutdown.

Where wet collection fits

  • As a polishing stage after a bag filter where SO2 also needs reduction and an alkali supply is available.
  • On small boilers where the limit is 100 mg/Nm3 and a bag house will not fit.
  • Where flue gas is hot and wet and cooling is needed anyway before the stack.
  • Not as a replacement for a bag filter where the limit is 30 mg/Nm3 or lower.

Energy is the other operating cost. A venturi at 5 kPa on 30,000 Nm3/h absorbs about 50 kW at the fan shaft, roughly 300,000 kWh a year at 6,000 hours, which usually exceeds the annual water bill. Compare total annual cost, not capital cost.

Measurement is the last trap. Wet gas sampling needs heated lines and a method that accounts for water vapour; a dry-basis analyser fed wet gas reports a number that satisfies nobody at the acceptance test.

XBOILER COMPANY specifies wet systems only when the water balance and wastewater route are confirmed by the plant. A scrubber without a water treatment plan is a maintenance liability dressed as an environmental solution.