A thermal oil heater looks like a boiler and is not one. There is no phase change, no steam drum and no classical water treatment. A pump circulates mineral or synthetic oil through a closed loop, the heater adds heat through a coil, and the oil releases that heat at a user – a reactor jacket, a press platen, a dryer, an asphalt tank. Understanding the system means understanding three things at once: the coil, the expansion tank and the circulation.
The closed loop and its four elements
The loop has a heater, a circulation pump, one or more users, and an expansion tank with deaeration. Oil leaves the heater at 280 to 320 °C, passes through the user, returns at 260 to 290 °C depending on the temperature drop designed for the process, and re-enters the pump. The temperature difference across the loop, typically 20 to 40 °C, sets the flow rate. At 1 MW and a 30 °C drop, with a specific heat near 2.6 kJ/kg·K and a density around 800 kg/m3 at 300 °C, the flow is about 40 m3/h. Flow, not temperature, is the variable that protects the coil.
Coil design and the flue gas path
The heating coil is a helical or serpentine arrangement of seamless steel tubes, usually 32 to 76 mm outside diameter, inside an insulated shell. In a vertical unit the burner fires down the centre and flue gas turns at the bottom and rises through the coil bundle; in a horizontal unit the gas passes along the shell and leaves through a chimney at the rear. Oil velocity inside the tube is deliberately kept at 2 to 4 m/s, high enough to keep the film temperature close to the bulk temperature. That matters: if flow drops, the tube wall can overheat long before the outlet sensor notices, and coke forms on the inner surface. Most coil failures begin as flow-related overheating, not as corrosion.
The expansion tank and deaeration
Thermal oil expands by roughly 0.0007 to 0.001 per °C. A 5 m3 system heated from 20 to 300 °C gains about 1.0 to 1.4 m3, and that volume has to go somewhere. The expansion tank provides the space, plus residence time for entrained gas and water to separate. It connects to the loop through an expansion line, usually at the pump suction, and is normally blanketed with nitrogen or held at slight positive pressure to limit oxidation. Tank level should run between 30 and 70% at operating temperature. A rising level with no top-up means water or decomposition gas is entering; a falling level means a leak or a closed valve on the expansion line.
- Tank volume: 25 to 35% of total system volume.
- Expansion line sized for 2 to 3 m/s oil velocity.
- Vent line routed to a safe outdoor location, never capped.
- Low level alarm at 20%, burner trip at 10%.
Circulation pump and flow protection
The pump is normally a horizontal centrifugal unit with a mechanical seal rated for 350 °C, often water-cooled. Two pumps in parallel with one standby is standard for processes that cannot stop. A differential pressure switch across the heater, or a flow meter on the outlet, must trip the burner if flow falls below about 70% of design. A low-flow trip is not optional equipment: it is the primary protection for the coil. Bypass control around the user is used during startup to bring the loop up to temperature gradually, avoiding thermal shock and keeping velocity in the coil above the minimum while users are still cold.
Controls and safety interlocks
- Low flow: trip the burner below 70% design flow.
- High outlet temperature: trip at 10 to 15 °C above setpoint, on an independent sensor.
- Low expansion tank level: alarm at 20%, trip at 10%.
- High flue gas temperature: alarm at 30 °C above normal, indicating fouling or low flow.
- Pump failure: trip the burner and keep a standby pump running to remove residual heat.
- Nitrogen blanket pressure low: alarm, because air ingress accelerates oil oxidation.
Typical system parameters
| Parameter | Typical value |
|---|---|
| Heat output | 0.35 to 14 MW |
| Outlet temperature | 250 to 320 °C, synthetic oils to 350 °C |
| Temperature drop across loop | 20 to 40 °C |
| Coil oil velocity | 2 to 4 m/s |
| System pressure | 0.4 to 1.0 MPa, essentially pump head only |
| Expansion tank volume | 25 to 35% of system volume |
| Thermal efficiency | 88 to 92%, or 90 to 93% with air preheater |
The absence of pressure is the main attraction. Oil at 300 °C needs only enough pressure to overcome pipe friction, perhaps 0.6 MPa, where saturated steam at the same temperature would need over 8.5 MPa. That is why thermal oil dominates in asphalt, chemical and textile plants where high temperature and low pressure must coexist, and why the coil, not the shell, becomes the component that decides system life. XBOILER COMPANY supplies heaters with the expansion tank, pump set and interlocks matched to the loop volume, so the flow protection is sized for the coil rather than added afterwards.